Pluggable
module, visual fault signalling, module locking.
- Three-pole
high performance lightning current arrester, leakage current-free.
- Installation
at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution
boards.
- For
protection against impact of direct or indirect lightning strikes in wide range
of applications – houses, office and industrial buildings.
- Coordination with SPD type 2 (SLP-275 V) even without surge separating inductors.
Specifications:
| rameter name | Parameter value | |
| Type
  of SPD | T1 | |
| Mounting | DIN rail 35 mm | |
| Nominal
  voltage | Un | 230 V AC | 
| Maximum
  operating voltage | Uc | 260.00 V AC | 
| Nominal
  load current for "V" connection | IL | 125 A | 
| Type
  of network | TN | |
| Maximum
  overcurrent protection | 250 A gL/gG | |
| Maximum
  overcurrent protection for "V" connection | 125 A gL/gG | |
| Short-circuit
  current rating | ISCCR | 50.0 kA | 
| Total
  discharge current (10/350 µs) | ITotal(10/350) | 75.00 kA | 
| Lightning
  impulse current (10/350 µs) | Iimp | 25.00 kA | 
| Voltage
  protection level | Up | 1.50 kV | 
| Response
  time | ta | 100 ns | 
| TOV
  5 s L-N | 335 V | |
| TOV
  characteristic (TOV 5 s) | withstand | |
| Cross-section
  of connected conductors solid (min) | 2.50 mm2 | |
| Cross-section
  of connected conductors solid (max) | 50.00 mm2 | |
| Cross-section
  of connected conductors stranded (min) | 2.50 mm2 | |
| Cross-section
  of connected conductors stranded (max) | 35.00 mm2 | |
| Fault
  indication | red indication field | |
| Remote
  indication | no | |
| Degree
  of protection | IP 20 | |
| Range
  of ambient temperatures (min/max) | -40 / 80 °C | |
| Humidity | 5 - 95 % | |
| According
  to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
| ETIM
  Class | EC000381 | |
| Plug
  module | FLP-25-T1-V/0 | |
| Customs
  tariff number | 85363090 | |
| EAN | 8595090553007 | 
Dimensions:
Replacement module: FLP-25-T1-V/0
Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..