Pluggable module, visual fault signalling, module
locking, remote fault signalling.
- Three-pole varistor lightning current
arrester.
- Installation at the boundary of zones LPZ 0
and LPZ 1 or higher, for objects in LPL III and IV.
- For protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
| Parameter name | Parameter value | |
| Type
  of SPD | T1,T2 | |
| Mounting | DIN rail 35 mm | |
| Nominal
  voltage | Un | 230 V AC | 
| Maximum
  operating voltage | Uc | 275.00 V AC | 
| Maximum
  operating voltage | Uc | 350.00 V DC | 
| Type
  of network | TN | |
| Maximum
  overcurrent protection | 160 A gL/gG | |
| Short-circuit
  current rating | ISCCR | 50.0 kA | 
| Total
  discharge current (10/350 µs) | ITotal(10/350) | 37.50 kA | 
| Lightning
  impulse current (10/350 µs) | Iimp | 12.50 kA | 
| Nominal
  discharge current (8/20 µs) | In | 30.00 kA | 
| Maximum
  discharge current (8/20 µs) | Imax | 60.00 kA | 
| Voltage
  protection level | Up | 1.50 kV | 
| Voltage
  protection level at 5 kA | Up | 0.90 kV | 
| Response
  time | ta | 25 ns | 
| TOV
  5 s L-N | 335 V | |
| TOV
  characteristic (TOV 5 s) | withstand | |
| Cross-section
  of connected conductors solid (min) | 1.00 mm2 | |
| Cross-section
  of connected conductors solid (max) | 35.00 mm2 | |
| Cross-section
  of connected conductors stranded (min) | 1.00 mm2 | |
| Cross-section
  of connected conductors stranded (max) | 25.00 mm2 | |
| Cross-section
  of remote indication conductors solid (max) | 1.5 mm2 | |
| Cross-section
  of remote indication conductors stranded (max) | 1.5 mm2 | |
| Fault
  indication | red indication field | |
| Remote
  indication | potential-free change-over contact | |
| Remote
  indication contacts | 250V/0,5A AC,250V/0,1A DC | |
| Degree
  of protection | IP 20 | |
| Range
  of ambient temperatures (min/max) | -40 / 80 °C | |
| Humidity | 5 - 95 % | |
| According
  to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
| ETIM
  Class | EC001457 | |
| Plug
  module | FLP-12,5 V/0 | |
| Customs
  tariff number | 85363090 | |
| EAN | 8595090534266 | 
Dimensions:
Replacement module: FLP-12,5 V/0
Lightning current and surge arrester , TN-C, 37.5 kA (10/350 µs), 180 kA (8/20 µs)
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.