Pluggable module,
visual fault signalling, remote fault signalling.
- Varistor
surge arrester.
- Installation
to LV installations, especially to sub-distribution boards.
- For
protection of the installations and equipments against impact of induced
overvoltages during a lightning strike or switching overvoltages.
- Suitable for protection of inverters or wind power plant systems.
Specifications:
| ameter name | Parameter
   value | |
| Type of SPD | T2 | |
| Mounting | DIN
  rail 35 mm | |
| Nominal voltage | Un | 230,00–690,00
  V AC | 
| Maximum operating voltage | Uc | 760.00
  V AC | 
| Maximum operating voltage of
  varistor | 880
  V AC | |
| Type of network | TN | |
| Maximum overcurrent protection | 100
  A gL/gG | |
| Short-circuit current rating | ISCCR | 25.0
  kA | 
| Nominal discharge current (8/20 µs) | In | 20.00
  kA | 
| Maximum discharge current (8/20 µs) | Imax | 40.00
  kA | 
| Voltage protection level | Up | 3.20
  kV | 
| Voltage protection level at 5 kA | Up | 2.70
  kV | 
| Response time | ta | 25
  ns | 
| Cross-section of connected
  conductors solid (min) | 1.00
  mm2 | |
| Cross-section of connected
  conductors solid (max) | 35.00
  mm2 | |
| Cross-section of connected conductors
  stranded (min) | 1.00
  mm2 | |
| Cross-section of connected
  conductors stranded (max) | 25.00
  mm2 | |
| Cross-section of remote indication
  conductors solid (max) | 1.5
  mm2 | |
| Cross-section of remote indication
  conductors stranded (max) | 1.5
  mm2 | |
| Fault indication | red
  indication field | |
| Remote indication | potential-free
  change-over contact | |
| Remote indication contacts | 250V/0,5A
  AC,250V/0,1A DC | |
| Degree of protection | IP
  20 | |
| Range of ambient temperatures
  (min/max) | -40
  / 80 °C | |
| Humidity | 5
  - 95 % | |
| According to standard | EN
  61643-11:2012, IEC 61643-11:2011 | |
| ETIM Class | EC000941 | |
| Plug module | SLP-600
  V/0 | |
| Customs tariff number | 85363030 | |
| EAN | 8595090533023 | 
Dimensions:
Replacement module:
SLP-600 V/0
Surge arrester ,TN and TT systems, , 690 V AC
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..