Fault signalling
by supply interruption.
- Surge
protection especially for LED lights.
- Installation
close to protected equipment in LV power circuits.
- Also for equipment in external part of building with low exposure level (according to IEEE C62.41.2).
Specifications:
| ameter name | Parameter
   value | |
| Type of SPD | T3 | |
| Mounting | installation
  box | |
| Nominal voltage | Un | 230
  V AC | 
| Maximum operating voltage | Uc | 320.00
  V AC | 
| Nominal load current | IL | 5.000
  A | 
| Maximum overcurrent protection | B
  16 A | |
| Short-circuit current rating | ISCCR | 1.5
  kA | 
| Nominal discharge current (8/20 µs)
  L-N | In | 3.00
  kA | 
| Nominal discharge current (8/20 µs)
  L+N-PE | In | 5.00
  kA | 
| Nominal discharge current (8/20 µs)
  N-PE | In | 3.00
  kA | 
| Test voltage L-N | Uoc | 6.0
  kV | 
| Test voltage L+N-PE | Uoc | 10.0
  kV | 
| Test voltage L-PE | Uoc | 6.0
  kV | 
| Test voltage N-PE | Uoc | 6.0
  kV | 
| Voltage protection level mode L-N | Up | 1.50
  kV | 
| Voltage protection level mode L-PE | Up | 1.50
  kV | 
| Voltage protection level mode N-PE | Up | 1.50
  kV | 
| Response time L-N | ta | 25
  ns | 
| Response time N-PE | ta | 100
  ns | 
| Fault indication | loss
  of voltage | |
| Remote indication | potential
  open contact | |
| Maximum current of signalling | 1.00
  A | |
| Degree of protection | IP
  20 | |
| Range of ambient temperatures
  (min/max) | -40
  / 80 °C | |
| Humidity | 5
  - 95 % | |
| According to standard | EN
  61643-11:2012, IEC 61643-11:2011 | |
| ETIM Class | EC000942 | |
| Customs tariff number | 85363010 | |
| EAN | 8595090567400 | 
Dimensions:
Module of surge ,6 A, installation C Low
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..