Pluggable module,
visual fault signalling, module locking.
- Varistor
lightning current arrester and surge arrester in 'U' connection.
- For
protection of PV systems on the roofs, where the separating spark-over distance
is not kept (connection to LPS).
- Maximum continuous operating voltage for PV application: UCPV ≥ 1.2x UOC STC.
Specifications:
| ameter name | Parameter
   value | |
| Type of SPD | PV
  T1, PV T2 | |
| Mounting | DIN
  rail 35 mm | |
| Maximum operating voltage mode +/PE,
  -/PE | UCPV | 280.00
  V DC | 
| Short-circuit current rating | ISCPV | 10
  000 A DC | 
| Residual current mode +/PE, -/PE | IPE | 0.500
  mA AC | 
| Residual current mode +/PE, -/PE | IPE | 0.020
  mA DC | 
| Total discharge current (10/350 µs) | ITotal(10/350) | 25.00
  kA | 
| Lightning impulse current (10/350
  µs) | Iimp | 12.50
  kA | 
| Total discharge current (8/20 µs) | ITotal(8/20) | 120.00
  kA | 
| Nominal discharge current (8/20 µs) | In | 30.00
  kA | 
| Maximum discharge current (8/20 µs) | Imax | 60.00
  kA | 
| Voltage protection level mode +/- | Up | 2.50
  kV | 
| Voltage protection level mode +/PE,
  -/PE | Up | 1.30
  kV | 
| Response time | ta | 25
  ns | 
| Cross-section of connected
  conductors solid (min) | 1.00
  mm2 | |
| Cross-section of connected
  conductors solid (max) | 35.00
  mm2 | |
| Cross-section of connected
  conductors stranded (min) | 1.00
  mm2 | |
| Cross-section of connected
  conductors stranded (max) | 25.00
  mm2 | |
| Fault indication | red
  indication field | |
| Degree of protection | IP
  20 | |
| Range of ambient temperatures
  (min/max) | -40
  / 80 °C | |
| According to standard | EN
  61643-31, IEC 61643-31 | |
| ETIM Class | EC001457 | |
| Plug module | FLP-PV275U
  V/0 | |
| Customs tariff number | 85363090 | |
| EAN | 8595090574071 | 
Dimensions:
Lightning current and surge arrester for PV systems,280 V DC
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..