Visual
fault signalling.
- Varistor
lightning current arrester and surge arrester in 'Y' connection.
- For
protection of PV systems on the roofs, where the separating spark-over distance
is not kept (connection to LPS).
- Maximum continuous operating voltage for PV application: UCPV ≥ 1.2x UOC STC.
Specifications:
| Parameter name | Parameter value | |
| Type of SPD | PV T1,
  PV T2 | |
| Mounting | DIN rail
  35 mm | |
| Maximum operating voltage mode +/PE, -/PE | UCPV | 1 500.00
  V DC | 
| Short-circuit current rating | ISCPV | 10 000 A
  DC | 
| Residual current mode +/PE, -/PE | IPE | 1.000 mA
  AC | 
| Residual current mode +/PE, -/PE | IPE | 0.010 mA
  DC | 
| Total discharge current (10/350 µs) | ITotal(10/350) | 12.50 kA | 
| Lightning impulse current (10/350 µs) | Iimp | 6.25 kA | 
| Total discharge current (8/20 µs) | ITotal(8/20) | 80.00 kA | 
| Nominal discharge current (8/20 µs) | In | 20.00 kA | 
| Maximum discharge current (8/20 µs) | Imax | 40.00 kA | 
| Voltage protection level mode +/- | Up | 5.40 kV | 
| Voltage protection level mode +/PE, -/PE | Up | 5.40 kV | 
| Response time | ta | 25 ns | 
| Cross-section of connected conductors solid (min) | 4.00 mm2 | |
| Cross-section of connected conductors solid (max) | 35.00 mm2 | |
| Cross-section of connected conductors stranded (min) | 2.50 mm2 | |
| Cross-section of connected conductors stranded (max) | 25.00 mm2 | |
| Fault indication | red
  indication field | |
| Degree of protection | IP 20 | |
| Range of ambient temperatures (min/max) | -40 / 80
  °C | |
| According to standard | EN 61643-31,
  IEC 61643-31 | |
| ETIM Class | EC001457 | |
| Customs tariff number | 85363090 | |
| EAN | 8595090542001 | 
Dimensions:
Lightning current and surge arrester for PV systems,1500 V DC
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..