•  DP-060-V/1-F16

Protection of power supply with output from the midle and non-grounded pole, also for powwer suply with

one pole grounded. Installation as close as possible to the protected equipment.

Technical specifications

Type of SPD

 

T3, C2

Connection (input - output) 

 

terminals-terminals

Location of SPD 

 

ST 2

Nominal voltage

Un

60V AC

Maximum operating voltage 

Uc

75V AC and 75V DC

Nominal load current 

IL

16,000A

C2 nominal discharge current (8/20 µs) per core 

In

2,00kA

C2 voltage protection level mode core-core at In

Up

390V

C2 voltage protection level mode core-PE at In 

Up

750,00V

Test voltage L+ - L- 

 

4,0kV

Test voltage L+(L-)-PE 

 

4,0kV

Test voltage M-PE 

 

4,0kV

voltage protection level L+ - L- 

 

0,39 kV

voltage protection level L+(L-)-PE

 

0,75 kV

voltage protection level M-PE 

 

0,75 kV

Maximum overcurrent protection 

 

16 A gL/gG or B 16 A

Response time L+ - L-

 

25ns

Response time L+(L-)-PE 

 

100ns

Response time M-PE 

 

100ns

Cross-section of connected conductors solid (min) 

 

0,14mm2

 

Cross-section of connected conductors solid (max) 

 

4,00 mm2

Cross-section of connected conductors stranded (min) 

 

0,14 mm2

Cross-section of connected conductors stranded (max)

 

2,50 mm2

Fault indication

 

red indicator

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-70 °C

Mounting 

 

DIN rail 35 mm


Write a review

Note: HTML is not translated!
Captcha

DP-060-V/1-F16

0 reviews / Write a review

* Required fields



Related Product

Manual shear for wires and cable

Manual shear for wires and cable

Specificationø mm<-->kg8-16650 mm2,2..

Cable Pulling Grip With One Eye 60 - 80mm L800mm.

Cable Pulling Grip With One Eye 60 - 80mm L800mm.

Cable pulling grip made of steel for cables ø 60 - 80 mm.With single eye and thimble, total length ..

FO Patch Cord 9/125 Dpx OS2 2.0mm SC/APC-SC/UPC-20m LSOH

FO Patch Cord 9/125 Dpx OS2 2.0mm SC/APC-SC/UPC-20m LSOH

Application:FTTH Telecommunication network. CATV system. Local Area Network. Active/P..

Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)

Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)

Pluggable module, visual fault signalling, module locking.Three-pole high performance lightning curr..