Specification:
- Standard safety models consist of a combined
overvoltage protection/mains filter element.
- Protects against transient overvoltages from
the mains, which, for example, are caused by switching machines on and off.
- When critical overvoltages occur, connection
to the mains is cut off.
- Once the protective conductor has been
triggered, the green function display light is not illuminated. The socket
strip can thus no longer be used.
- Basic equipment protection is classified as
class 3 (category D).
- For optimal protection, class 1 and 2
(categories B and C) protective equipment must be installed in the building.
- High-frequency glitches are generally caused
by switching processes in an operation from 100 kHz to 5MHz.
- This high-frequency rate overloads the mains
frequency and affects adjacent electronic equipment. The mains filter
attenuates this high-frequency rate.
- The attenuation behavior is harmonized with
the typical interference spectrum.
- 19" installation option (for length 483
mm).
- Socket rotation: 45°.
- Feed cable:HO5VV-F 3G 1.5 mm2.
- Molded right angle plug.
Material/ Finish:
- Housing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
- Plastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
- Internal conductor: full-length busbars,
brass.
Dimensions:
- Distance between sockets: 50 mm.
- Height: 45.5 mm.
- Width of housing: 44.4 mm (= 1 U).
- Feed cable: 2.5 m.
Color combination
Final digit of order number .1:
- RAL 7035, light-grey.
Final digit of order number .6:
- housing RAL 2003 pastel orange.
Plastic parts:
- RAL 7035, light-grey.
Technical data:
- Mains voltage: 230 VAC.
- Nominal current: max. 16 A / 10 A.
- Discharge surge current (8/20 s): 10 kA.
- Reaction time: ‹ 25 ns.
- Safety level (at100 A varistor peak
current): L with respect to N: ‹ 800 V, L / N with respect to PE: ‹ 1500 V.
- Overvoltage protection.
- Appliance class: Class 3 – as per DIN EN
61643-11.
- Requirement class: Category D as per VDE
0675-6.
- Mains filter: as per VDE 0565 (EN 60939).
Supply schedule:
- 1 x socket strip.
- 2 x mounting brackets.
|
Input
values |
Input
Connector |
Outputs |
L |
S |
F1 |
Part
No. |
|
|
Voltage |
Current |
D |
|
|
|
|
|
|
230 V |
16A |
Schuko CEE7/7 |
13 |
883 |
S |
F1 |
03.318.013.X |
Knürr DI-STRIP® Safety Standard (D Schuko– 13, L - 883).
Related Product
Knürr DI-STRIP® Safety Standard (D Schuko– 9, L - 683).
Specification:Standard safety models consist of a combined overvoltage protection/mains filter elem..
Knürr DI-STRIP® Safety Standard (D Schuko– 9, L - 732).
Specification:Standard safety models consist of a combined overvoltage protection/mains filter elem..
Knürr DI-STRIP® Safety Standard (D Schuko– 13, L - 883).
Specification:Standard safety models consist of a combined overvoltage protection/mains filter elem..
Knürr DI-STRIP® Safety Basic (F UTE– 6, L - 483).
Specification:For protection against transient overvoltage from the mains, which, for example, are ..