Specification:
- Standard
safety models consist of a combined overvoltage protection/mains filter
element.
- Protects
against transient overvoltages from the mains, which, for example, are caused
by switching machines on and off.
- When
critical overvoltages occur, connection to the mains is cut off.
- Once
the protective conductor has been triggered, the green function display light
is not illuminated. The socket strip can thus no longer be used.
- Basic equipment protection is classified as class 3 (category D).
- For
optimal protection, class 1 and 2 (categories B and C) protective equipment
must be installed in the building.
- High-frequency
glitches are generally caused by switching processes in an operation from
100 kHz to 5MHz.
- This
high-frequency rate overloads the mains frequency and affects adjacent
electronic equipment. The mains filter attenuates this high-frequency rate.
- The
attenuation behavior is harmonized with the typical interference spectrum.
- 19"
installation option (for length 483 mm).
- Socket
rotation: 45°.
- Feed
cable:HO5VV-F 3G 1.5 mm2.
- Molded
right angle plug.
Material/
Finish:
- Housing:
closed sheet steel extrusion, zinc-passivated, powder-coated texture.
- Plastic
parts: Vampamid 6 0024 VO (UL94), recyclable.
- Internal
conductor: full-length busbars, brass.
Dimensions:
- Distance
between sockets: 50 mm.
- Height:
45.5 mm.
- Width
of housing: 44.4 mm (= 1 U).
- Feed cable: 2.5 m.
Color
combination
Final
digit of order number .1:
- RAL
7035, light-grey.
Final
digit of order number .6:
- housing
RAL 2003 pastel orange.
Plastic
parts:
- RAL
7035, light-grey.
Technical
data:
- Mains
voltage: 230 VAC.
- Nominal
current: max. 16 A / 10 A.
- Discharge
surge current (8/20 s): 10 kA.
- Reaction
time: ‹ 25 ns.
- Safety
level (at100 A varistor peak current): L with respect to N: ‹ 800 V, L / N with
respect to PE: ‹ 1500 V.
- Overvoltage
protection.
- Appliance
class: Class 3 – as per DIN EN 61643-11.
- Requirement
class: Category D as per VDE 0675-6.
- Mains
filter: as per VDE 0565 (EN 60939).
Supply
schedule:
- 1 x
socket strip.
- 2 x mounting brackets.
|
Input values |
Input Connector |
Outputs |
L |
S |
F1 |
19” |
Part No. |
|
|
Voltage |
Current |
D |
|
|
|
|
|
|
|
230 V |
16A |
Schuko
CEE7/7 |
5 |
483 |
S |
F1 |
19” |
03.318.005.X |
Knürr DI-STRIP® Safety Standard (D Schuko– 5, L - 482).
Related Product
Knürr DI-STRIP® Combi (D Schuko– 5, L - 533).
Specification:Master-slave with overvoltage protection and mains filter. Automatic consumer switch..
Knürr DI-STRIP® Combi (D Schuko– 9, L - 732).
Specification:Master-slave with overvoltage protection and mains filter. Automatic consumer switch..
Knürr DI-STRIP® Master-Slave (F UTE– 5, L - 483).
Specification:Slave plugs will switch on if master switches on. Note: The master consumer's power..
Knürr DI-STRIP® Master-Slave (D Schuko– 5, L - 483).
Specification:Slave plugs will switch on if master switches on. Note: The master consumer's power..