Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 24 RACK PANEL
Related Product
VOLTAFIX • ø 7,5 mm - Accessories and spare parts
Starting/Ending ends with M12 thread, for rod ø 7,5 mmSpecificationPart Numberø mmgrGVFIR1136..
Cable Internal 4pr SFTP CAT6 LSOH 500m/Roll - Grey
Diameter of conductor : 24AWGInsulation : Pe 1,10 mmCable assembly : pair | Number of pairs: 4Cross ..
AED 3.50
BNC Plug 75 Ohms CR/CR G31 RG11A/U
The BNC series is the most commonly used coax connector. With its bayonet coupling mechanism this co..
AED 26.67
Slide in filter cassette
Filter cassette with railsFor installation in Dacobas 19” cabinetsFilters intake airComfortably remo..