Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,20dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 16 RACK PANEL
Related Product
Die Replacement HT-5333D2 (RG58/59/62/11/8/213)
Specification Type no HTDie P/NSpecificationsCrimping Cable Size 336D2 3D2.256”..
AED 45.00
Open Frame Base 19" D600 RAL9005
Open Frames RS SeriesThe RS frame series are best suited for closed rooms with controlled access and..
AED 175.00
Adapters and Cables
Adapters and Cables used to complete your PDU installation. Cables and AdaptersDescriptionPart ..
AED 30.00
Fine surge protector, LPZ 1 - LPZ 2 boundary installation, up to 60v
Fine protector for Ethernet networks with PoE and general structured cabling.Fine surge protector ..