• DL-Cat. 5e 8 RACK PANEL

Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the

boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.

Technical specifications

Type of SPD

 

C2,C3

Location of SPD 

 

ST 3

Maximum operating voltage 

Uc

6V DC and 8V DC

Nominal load current

IL

0,100A

C2 nominal discharge current (8/20 µs) per core

In

0,20kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

1,60kA

C2 voltage protection level mode core-core at In 

Up

40V

C2 voltage protection level mode core-PE at In 

Up

350V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

65V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-core 

ta

100ns

Insertion attenuation at 250 MHz 

 

1,50dB

Connection (input - output)

 

RJ 45/RJ 45

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

60 °C

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC000943

Write a review

Note: HTML is not translated!
Captcha

DL-Cat. 5e 8 RACK PANEL

* Required fields


Terms & Conditions
  • All prices are subject to confirmation and exclude applicable taxes unless stated otherwise.
  • Payment terms are outlined in the respective quotation or invoice.
  • Orders will be processed once payment is confirmed or an approved purchase order is received, where applicable.
  • Prices, availability, and payment terms are subject to change without prior notice.

Related Product

75-Ohm BNC Male Crimp Connector For HD Video & CCTV Coax

75-Ohm BNC Male Crimp Connector For HD Video & CCTV Coax

The BNC series is the most commonly used coax connector. With the bayonet coupling this connector ca..

AED13.06

Surge protection for Ethernet 1 Gbit/s (Cat. 6) or 10 Gbit/s (Cat. 6A), 2 kA (10/350 µs).

Surge protection for Ethernet 1 Gbit/s (Cat. 6) or 10 Gbit/s (Cat. 6A), 2 kA (10/350 µs).

RJ45 sockets, PCB, with injector.Combination of coarse and fine protection of Ethernet line with Po..

Patch Cord Booted CAT6 5m - Blue- Pressac

Patch Cord Booted CAT6 5m - Blue- Pressac

Patch Cord Booted CAT6 5m - Blue- Pressac..

IEC C14 To C15 Power Cord 3m For Data Center Equipment.

IEC C14 To C15 Power Cord 3m For Data Center Equipment.

Interconnecting Power leads & linksIEC 60320 - 10 Amp supplied with 1.5mm² Flex3 Metre male to f..