Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the
boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 8 RACK PANEL
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: DL-Cat. 5e 8 RACK PANEL
- MPN: 8595090529309
Terms & Conditions
- Product Information: Specifications, images and availability are subject to change without notice.
- Enquiries & Pricing: All enquiries and displayed prices are subject to availability and confirmation by Dafnia.
- Quotation & Payment: Final pricing, applicable taxes, delivery and payment terms will be stated in the quotation or invoice.
- Order Confirmation: Orders are confirmed only upon written acceptance by Dafnia and receipt of the agreed payment or approved purchase order, where applicable.
Related Product
Lightning current arrester for coaxial lines (antennas), 180 V DC
N connectors, 50 Ohm.Lightning current arrester for coaxial line.Installation at the boundary of LPZ..
Lightning current arrester , replacement module for 2-core signalling lines, 230 V DC, max. 1 A
Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT..
45-Degree Ergonomic Desk Corner Connector with Mounting Kit
45° Triangle corner with corner frame and mounting material A B ..
Plinth Fixed W600 D600 - RAL7035
For doubleprorack stand-alone enclosuresWith levelling feetWith ventilation useHeight = 100 mm..