Protection of line and communication interfaces of the PROFIBUS industrial bus-bar system. Coarse and fine surge protection. Also, cable shielding is protected.
Parameters
Type of SPD | C2,C3 | |
Connection (input - output) | terminals-terminals | |
Location of SPD | ST 2+3 | |
Nominal voltage | Un | 5V DC |
Maximum operating voltage | Uc | 6V AC |
Maximum operating voltage | Uc | 8V AC |
Nominal load current | IL | 0,060 A |
C2 nominal discharge current (8/20 µs) core-core | In | 10,00Ka |
C2 voltage protection level mode core-core at In | Up | 150 V |
C2 voltage protection level mode core-COM at In | Up | 150 V |
C2 voltage protection level mode COM-PE at In | Up | 350 V |
C2 voltage protection level mode SH-PE at In | Up | 350 V |
C3 voltage protection level mode core-core at 1 kV/µ | Up | 40 V |
C3 voltage protection level mode core-COM at 1 kV/µs | Up | 40 V |
C3 voltage protection level mode COM-PE at 1 kV/µs | Up | 650 V |
C3 voltage protection level mode SH-PE at 1 kV/µs | Up | 650 V |
Response time core-core | ta | 1 ns |
Response time core COM |
| 1 ns |
Response time COM-PE | ta | 100ns |
Response time SH-PE | ta | 100ns |
Serial resistance per core | R | 1,00Ω |
Treshold frequency core-core | f | 100,00MHz |
Cross-section of connected conductors solid - max |
| 400 mm2 |
Cross-section of connected conductors stranded - max |
| 2,50 mm2 |
Degree of protection |
|
DM-PROFIBUS 5 V
Terms & Conditions
Related ProductGalvanised corner cable guiding rollers for manholesSpecificationPart Number<-->kgJZSUR 866a90mm1200-170028JZSUR 866b101mm1200-170034JZSUR 866c114.. Quick-Drying Nonflammable Fiber Optic Cleaner Solvent 225mlProduct Features:For use with Viavi Solutions® CLEANBLAST fiber end-face cleaning systemsCleans dust.. Straight 75 Ohm BNC Male Crimp Connector for HD VideoThe BNC series is the most commonly used coax connector. With its bayonet coupling mechanism this co.. Mechanical drum trestleSpecificationPart NumberkgJZCAM015T1'500400-1800mm7430JZCAM030T3'000700-2600mm10064JZCAM050T5'000930.. |