two-stage protection of Ethernet, instalation at the entrance of th line into the stucture and close to equipment,
at the boundary of LPZ 0 and LPZ 1 or higher, for protection of Ethernet network Cat. 6 against surge over voltage
Technical specifications
Type of SPD | | D1,C2,C3 |
Location of SPD | | ST 1+2+3 |
Maximum operating voltage | Uc | 9V DC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 0,15kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
D1 total discharge current (10/350 µs) cores-PE | ITotal | 2,00kA |
C2 voltage protection level mode core-core at In | Up | 50V |
C2 voltage protection level mode core-PE at In | Up | 400V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 20V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | | IP 20 |
Range of operating temperatures - min | | -40 °C |
Range of operating temperatures - max | | 80 °C |
ETIM Class | EC000943 | |
According to standard | | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 |
DL-1G-RJ45-5V
Related Product
Slide in filter cassette
Filter cassette with railsFor installation in Dacobas 19” cabinetsFilters intake airComfortably remo..
Coupler Inline RJ45F To RJ45F CAT6
CAT6 inline couplerUTP RJ45Jack-to-Jack typeHorizontal narrow (slim width = 16.3mm)SpecificationsRoH..
AED 6.50
Knürr Elicon® Computer Platform
FixedLow space requirement in the heightMounting height variableCan be upgraded at any timeEasy moun..
Patch Panel For Keystone CAT6A 1U 24Port UTP Unloaded
Unloaded Patch Panel 1U 24Port for Cat6A UTP Keystone Jack.Designed to accept Category 6-Augmented K..
AED 77.00