Protection of power supply with output from the midle and non-grounded pole. Installation as close as possible to the protected equipment.
Technical specifications
Type of SPD | T3, C2 | |
Connection (input - output) | terminals-terminals | |
Location of SPD | ST 2 | |
Nominal voltage | Un | 60V AC |
Maximum operating voltage | Uc | 75V AC |
Nominal load current | IL | 16,000A |
C2 nominal discharge current (8/20 µs) per core | In | 2,00kA |
C2 voltage protection level mode core-core at In | Up | 390V |
C2 voltage protection level mode core-PE at In | Up | 210v |
Test voltage L+ - L- | 4,0kV | |
Test voltage L+(L-)-PE | 4,0kV | |
voltage protection level L+ - L- | 0,39 kV | |
voltage protection level L+(L-)-PE | 0,21 kV | |
Maximum overcurrent protection | 16 A gL/gG or B 16 A | |
Response time L+ - L- | 25ns | |
Response time L+(L-)-PE | 100ns | |
Cross-section of connected conductors solid (min) | 0,14mm2 | |
Cross-section of connected conductors solid (max) | 4,00 mm2 | |
Cross-section of connected conductors stranded (min) | 0,14 mm2 | |
Cross-section of connected conductors stranded (max) | 2,50 mm2 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | -70 °C | |
Mounting | DIN rail 35 mm | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012, EN 61643-11:2012, IEC 61643-11:2011 |
DP-060-V/1-16
Related Product
Cable Control 2C 1.5sqmm LI2YY/16AWG UNSCN - 305m/Roll
ApplicationsThese PVC cables are used in industrial applications for signaltransmission. They can be..
AED 2.26
GIRAVOLTA • ø 3 mm- Accessories and spare parts
Cable pulling grip, M5 thread, ø 4-15 mmSpecificationPart NumberØ mmLmmNowiresØwireEconomyVersionSta..
Door Front Glass 37U W600 RAL7032
Material Sheet steel 1.0 mm, single safety glass panel, 4 mm cle..
Three-Phase Network Analyser - Class A
Main Specifications: Voltage input: 3 channels: 0-275/400 VRMS (400/690 V available as an optio..