• CLSA-6

Product Description

Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

6V AC

Maximum operating voltage 

Uc

9V AC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

13V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

1,50MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-70 °C

ETIM Class 

 

EC001625

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

 

Write a review

Note: HTML is not translated!
Captcha

CLSA-6

0 reviews / Write a review

* Required fields



Related Product

Spare pair of blades

Spare pair of blades

PourJ02112006XVM-S1060 XVM-S1080- K101/1EJ02112007XVM-S1070- K101/2E..

Cable External FO 6C 9/125 CLT Steel ARM -Black

Cable External FO 6C 9/125 CLT Steel ARM -Black

Cable Type:     Loose Tube, Outdoor F/O Cable6 fib..

AED 3.53

Jensen Tools JTK-2100LM LAN Manager's kit without Test Equipment in Monaco Case

Jensen Tools JTK-2100LM LAN Manager's kit without Test Equipment in Monaco Case

SpecificationsDimensions (ID) (L x W x D)17-3/4" x 12-3/4" x 5"Case StyleMonacoCase Style No1Pallet ..

"Gliss Jetting" Lubricant for laying Fibreoptic cables with jetting technology