Combination of coarse and fine protection designed to protect data lines with high speed rates
Technical specifications
Type of SPD | C3,C2 | |
Connection (input - output) | LSA disconnection rail | |
Accessories | grounding rail | |
Location of SPD | ST 2+3 | |
Maximum operating voltage | Un | 6V AC |
Maximum operating voltage | Uc | 9V AC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 500kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
C2 voltage protection level mode core-PE at In | Up | 350V |
C2 voltage protection level mode core-core at In | Up | 32V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 15V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Serial resistance per core | R | 1,60Ω |
Treshold frequency core-core | f | 55,00MHz |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 70 °C | |
Mounting | LSA disconnection rail | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001625 |
CLSA-HF6
Related Product
Surge protection for 3-core signalling lines, 6 V DC, max. 60 mA
Coupling impedance (R – resistance).Coarse and fine surge protection for 3-core signalling lines.Ins..
PDU 12 Way 19" IEC320 C13 3x1.5mm² C14 250VAC 10A Plug -2m
Horizontal Installation, cable entrance from left side ; internal structure with insulation pa..
AED 100.00
Surge protection for two 1-core signalling networks, 48 V DC, max. 0.5 A
Coupling impedance (resistance), screwless terminals.Coarse and fine surge protection for two 1-cor..
CDU Switched Link V26 C13 230V 1PH 2BR 32A,3Pin BU 10" BTM.
- Switched Expansion Module PDU, 0U, 32A, 230V, (16)C13R, IEC60309 Input PThe Server Tech CX-16VE-P3..